TEPG Electromagnetic Door Holder


Click to enlarge

The TEPG Electromagnetic Door Holder is designed to allow fire and smoke doors to be held open under normal conditions, but to automatically close under their own spring return mechanism when a fire or smoke alarm system is activated.

  • Compact and attractive
  • Very low profile
  • 12V and 24V models
  • Low operating current: 24V, 50mA; 12V, 100mA
  • Holders have no moving parts
  • Suitable for surface or flush mounting
  • Mounts on electrical industry standard flush or surface box
  • Dimensions: Magnet 118h x 74w x 27d; Keeper Plate 75 dia, 23d
  • 25kg (approx.) holding force
  • Manual release button included
  • Resilient keeper accommodates angular non-alignment (15° max.)

Manuals

 Door Holder Installation Instructions
DC5000 Installation Instructions


EA0407 Electromagnetic Door Holder

 The EA0407 Electromagnetic Door Holder is designed to hold fire and smoke doors open under normal conditions, but automatically close under their own spring return mechanism when a fire or smoke alarm system is activated. The door is held open by the magnetic force between an electromagnet mounted on the wall behind the door and a keeper fixed to the back of the door. When the electrical supply to the electromagnet is interrupted, the electromagnet is de-energised and the door automatically closes.

Specifications

  • Operating Voltage: 24Vdc ± 20%
  • Operating Current: 50mA nominal
  • Operating Temp: 0 to 60°C
  • Relative Humidity: 95% (non-cond.)
  • Cable Termination: 2x1.5mm2
  • Holding Load: 25kg nom. @24V, 20°C
  • Dimensions: 150mm, 75 dia x 23mm (Plate)

EA0408 Electromagnetic Door Holder

 The EA0408 Electromagnetic Door Holder is designed to hold fire and smoke doors open under normal conditions, but automatically close under their own spring return mechanism when a fire or smoke alarm system is activated.The door is held open by the magnetic force between an electromagnet mounted on the wall behind the door and a keeper fixed to the back of the door. When the electrical supply to the electromagnet is interrupted, the electromagnet is de-energised and the door automatically closes.

Specifications

  • Operating Voltage: 24Vdc ± 20%
  • Operating Current: 50mA nominal
  • Operating Temp: 0 to 60°C
  • Relative Humidity: 95% (non-cond.)
  • Cable Termination: 2x1.5mm2
  • Holding Load: 25kg nom. @24V, 20°C
  • Dimensions: 300mm, 75 dia x 23mm (Plate)

EA0410 Electromagnetic Door Holder

 The EA0410 Electromagnetic Door Holder is designed to hold fire and smoke doors open under normal conditions, but automatically close under their own spring return mechanism when a fire or smoke alarm system is activated.The door is held open by the magnetic force between an electromagnet mounted on the wall behind the door and a keeper fixed to the back of the door. When the electrical supply to the electromagnet is interrupted, the electromagnet is de-energised and the door automatically closes.

Specifications

  • Operating Voltage: 24Vdc ± 20%
  • Operating Current: 50mA nominal
  • Operating Temp: 0 to 60°C
  • Relative Humidity: 95% (non-cond.)
  • Cable Termination: 2x1.5mm2
  • Holding Load: 25kg nom. @24V, 20°C
  • Dimensions: 150mm, 75 dia x 23mm (Plate)

EA0411 Electromagnetic Door Holder

 The EA0411 Electromagnetic Door Holder is designed to hold fire and smoke doors open under normal conditions, but automatically close under their own spring return mechanism when a fire or smoke alarm system is activated. The door is held open by the magnetic force between an electromagnet mounted on the wall behind the door and a keeper fixed to the back of the door. When the electrical supply to the electromagnet is interrupted, the electromagnet is de-energised and the door automatically closes.

Specifications

  • Operating Voltage 24Vdc ± 20%
  • Operating Current 50mA nominal
  • Operating Temp 0 to 60°C
  • Relative Humidity 95% (non-cond.)
  • Cable Termination 2x1.5mm2
  • Holding Load 25kg nom. @24V, 20°C
  • Dimensions 300mm, 75 dia x 23mm (Plate)

EA0405 Door Holder Release

The EA0405 Electromagnetic Door Holder Release is designed to allow fire and smoke doors to be opened manually. A standard switch plate mounting is used. A momentary action switch de-energised the door holder allowing the door to open.

Specifications

  • Operating Voltage 12/24Vdc
  • Maximum Current 12A
  • Operating Temp 0 to 60°C
  • Relative Humidity 95% (non-cond.)
  • Cable Termination 4x1.5mm2
  • Dimensions 74x118x30mm

Part Number

  • EA0405

SUO613 Emergency Door Release - Single Pole

The SU0613 Manual Call Point has a plastic coated frangible element to ensure safe and reliable operation, producing no dangerous glass shards. It is operated by simply pressing on the centre of the frangible element until it snaps. A hammer or other impact device is not required. The snapped frangible element releases a single pole microswitch. The SU0613 is a surface mounting, white MCP that includes a white back box to house the terminations. It is fitted with a green label carrying the words EMERGENCY DOOR RELEASE in white text. Switch function (NO/NC) is determined by the position of the terminal block.

Specifications

  • Max Current @ 30Vdc Resistive 8A Inductive 3A
  • Contact Resistance 100mOhm. (max)
  • Switch Single Pole
  • Operating Temp 0 to 60°C
  • Relative Humidity 95% (non-cond.)
  • Dimensions 87x87x52 mm
  • Legend Emergency Door Release

Part Numbers

  • SU0613 BGA
  • 515.001.025 Spare Glass (pk 5)

SUO614 Emergency Door Release - Double Pole

The SU0614 Manual Call Point has a plastic coated frangible element to ensure safe and reliable operation, producing no dangerous glass shards. It is operated by simply pressing on the centre of the frangible element until it snaps. A hammer or other impact device is not required. The snapped frangible element releases a double pole microswitch. The SU0614 is a surface mounting, white MCP that includes a white back box to house the terminations. It is fitted with a green label carrying the words EMERGENCY DOOR RELEASE in white text. There are 2 terminal blocks for connection. Switch function (NO/NC) is determined by the terminals used.

Specifications

  • Max Current @ 30Vdc Resistive 8A Inductive 3A
  • Contact Resistance 100mOhm. (max)
  • Switch Double Pole
  • Operating Temp 0 to 60°C
  • Relative Humidity 95% (non-cond.)
  • Dimensions 87x87x52 mm
  • Legend Emergency Door Release

Part Numbers

  • SU0614 DP BGA
  • 515.001.025 Spare Glass (pk 5)